Print Product Literature

Transformer Oil

Vega produces and markets transformer oils meeting IEC and ASTM standards. We stock and market transformer oils from three global locations i.e. USA, UAE and Pakistan. We have experienced team to test, handle, pack and ship transformer oil in Flexi containers and drums to our customers around the globe.

We have in house testing and research laboratory to test transformer oil as per IEC 60296 and ASTM D3487 standards and specifications.

VTO 60U: IEC 60296 Transformer Oil, Uninhibited

VTO 60NU: IEC 60296 Transformer Oil, Uninhibited (Naphthenic)

VTO 60Ni: IEC 60296 Transformer Oil, Inhibited (Naphthenic)

VTO 60U, Typical Specifications
PROPERTY TEST METHOD SPECIFICATION TYPICAL VALUES
Appearance IEC-296 Clear free from sediment and suspended Clear free from sediment and suspended
Density @ 29.5 °C Kg/m3 ISO-3675 - 0.853
Density @ 20 °C Kg/m3 ISO-3675 0.895 Max. 0.860
Kinematic Viscosity, mm2/s at 40 °C ISO-3104 12 Max. 10.43
Kinematic Viscosity, mm2/s at -30 °C ISO-3104 1800 Max. 270
Flash Point (PMCC) °C ISO-2719 135 Min. 146
Corrosive Sulphur DIN-51353 Non Corrosive Non Corrosive
Neutralization Value, mgKOH/gm. IEC-62021-1 0.01 Max. < 0.0002
Break Down Voltage (as delivered KV rms.) IEC-60156 30 KV rms. Min 70
DDF at 90 °C IEC-60247 0.005 Max. 0.0004
PCB Content, ppm IEC-61619 Not Detectable Not Detectable
Oxidation Stability (164 hrs)
1. Total Acidity, mg/KOH/gm
2. Sludge Content % by mass
3. DDF at 90 °C
IEC-61125 Method-C IEC-60247 1.2 Max.
0.8 Max.
0.5 Max.
0.22
0.081
0.058
Antioxidant additives, Mass IEC-60666 Not Detectable Not Detectable
Water Content, ppm in
Bulk, mg/kg
Bottle/Drum, mg/kg
IEC-60814 30 Max.
40 Max.
16
19
Pour Point °C ISO-3016 - 40 - 45
Interfacial Tension, N/m at 25 °C ISO-6295 40 Min. 46
2-Furfural Content, ppm IEC-61198 0.1 Max. Not Detectable
PCA Content, % by mass IP-346 3 Max. .60